Why triphosphor lamps are unsuitable for hospitals.

Following the introduction of higher-efficacy triphosphor lamps in the early 1980s, a large number were quickly installed in commercial buildings, including many hospitals. The standards committee decided they were not acceptable for clinical observation areas. This is why.

LL
LightLab Technical Team
Editor’s note. This is one in a historical series of documents published in our Lab Notes series around the turn of the century. The series is a snapshot of understanding at that time. We hope that you find it interesting.

Pressure to accept the new lamps

Triphosphor lamps were widely installed not only in Australia but in countries such as Britain and New Zealand. As a consequence there was much commercial pressure for these lamps to be written into the new Australian and New Zealand Standard on hospital lighting, AS/NZS 1680.2.5.

The matter was duly considered by the Standards Australia Committee LG/1. After long and careful deliberation, it decided not to include triphosphor lamps as acceptable for use in clinical observation areas.

The 1970s trials

In the early 1970s extensive trials were carried out at the Royal Prince Alfred Hospital in Sydney to ascertain which tubular fluorescent lamps were acceptable to assist in the early positive recognition of cyanosis. Cyanosis is a condition where a person turns blue for want of oxygen, and it is generally accepted that the cyanosis point is equivalent to 93% oxygen saturation of the blood.

The trials led to the adoption of a set of lamp colour temperature and colour rendering limits in the then Australian Standard AS 1765 - 1975, and to the widespread adoption in Australia of the Colour 37 lamp as the standard lamp for clinical observation. The problem with Colour 37 lamps is that although they have very high colour rendering, their luminous efficacy is relatively low. Because of this the more efficient triphosphor lamps were widely used as replacements.

Why the spectrum matters

It is generally recognised in medical literature that the detection of cyanosis requires adequate light in the 640 nm to 660 nm band. Light sources that lack energy in this band give the blood a false darker appearance. Sources with an excess of energy in this band give the blood a lighter appearance. Either way, the clinical judgement is misled.

The difficulty faced by the committee was that the range of triphosphor lamps then available had an unacceptably low level of energy in this critical band. Later experimental work at the Royal North Shore Hospital in Sydney, in conjunction with the School of Optometry at the University of New South Wales, showed that only a small change in the phosphor formulation would be needed to make these lamps acceptable.

Cyanosis observation index

Section 7 of AS 1680.2.5 recommends that in all areas of a hospital or health care facility where detection of cyanosis is important, the lamps should fall within specified colour temperature and colour rendering boundaries, and have a cyanosis observation index (COI) of not greater than 3.3, determined by the method set out in Appendix G of the standard.

The lower the COI value, the better suited the light source is to the visual detection of cyanosis, because a lower value means the source is a closer match to the reference. The reference source is a Planckian radiator, a thermal light source with a continuous energy distribution, at a colour temperature of 4000 K. The average colour difference for two representative blood samples is calculated under the test lamp and the reference source, and that average is the cyanosis observation index.