Unified Glare Rating explained.

Interior lighting standards offer two ways to limit the discomfort glare experienced by people at work: a luminaire selection system, or a glare evaluation system based on a calculated index. This Lab Note explains why the calculated approach became necessary.

LL
LightLab Technical Team
Editor’s note. This is one in a historical series of documents published in our Lab Notes series around the turn of the century. The series is a snapshot of understanding at that time. We hope that you find it interesting.

Two systems for limiting glare

The Australian Standard AS 1680.1 - 1990, Interior Lighting Part 1, provides two alternative systems for limiting the degree of discomfort glare experienced by occupants of interior workplaces: a luminaire selection system or a glare evaluation system. The latter is based on a calculated Glare Index (GI) value, and the AS 1680 series 2 standards include recommended maximum GI values.

The past decade has seen many changes with significant effects on lighting methodology: new types of lamps and luminaire technology, the almost universal acceptance of computer-aided design programs, radical changes in work practices and an increasing community awareness of the need for energy conservation. The 36 W compact fluorescent lamp brought another very high source of luminance into the workplace, approximately 25 kcd/m².

Prismatic panels and batwing luminaires

To maintain the same degree of glare limitation as the older 38 mm tubular fluorescent lamps, much tighter light control is necessary. The introduction of the batwing type of luminaire as a replacement for the prismatic lens panel was a major change for office lighting. The prismatic panel generally has a fairly symmetrical intensity distribution, whereas the batwing luminaire produces an asymmetrical one.

With a batwing luminaire the crosswise (C0) distribution is considerably different from the lengthwise (C90) distribution, which generally allows greater spacings in the C0 plane for the same uniformity of illuminance. Fewer luminaires are needed, which saves energy.

However, the C45 intensity distribution tends to be higher than the C0 distribution in the glare zone, the area between 45 degrees and 90 degrees from the nadir. The luminance distribution of the prismatic panel fits comfortably into the conventional tabular method or the luminance limiting graphical method of calculation. The batwing luminaire definitely does not.

As a general rule, installations that consist solely of recessed batwing luminaires tend to produce dull and gloomy interiors. If uplighting is added to the design the whole visual environment changes. Because of the lightened ceiling the Glare Index value is also reduced, and the revised value can be calculated with the formula-based method. Neither the tabular nor the luminance limiting methods can calculate a glare rating for this type of installation.

Changes in workplace practice

There have been two major changes in the modern office: the landscaped office with its random arrangement of desks and furniture, and the large-scale arrival of screen-based tasks.

In the offices of the 1940s the furniture was arranged in a rectilinear array, all facing the same direction. Two of the basic assumptions of discomfort glare were then valid: that the C0 and C90 planes were the predominant viewing directions, and that the worst case was in the middle of the back wall or the side wall. In a landscaped office the furniture often faces all points of the compass, so viewing directions vary.

Screen-based tasks have also raised the line of sight of the operator. More of the ceiling and the overhead luminaires come within the outer peripheral field of view, so more luminaires fall within the personal glare zone. In this way discomfort glare has again become a problem in the modern workplace.

The need for energy conservation

Clients are demanding higher-efficiency luminaires and lighting systems that use fewer of them. When conventional lens panels or reflector and louvre assemblies are used this way, more discomfort glare is usually experienced. The pressure is on luminaire designers to produce high-efficiency luminaires with low glare ratings at a reasonable cost.

Glare Index versus luminance limiting

In the past, compliance with luminance limiting values simply gave a rough indication that a luminaire or installation might create discomfort glare. The Glare Index system is more sensitive, and can be used to identify troublesome locations and viewing directions within a particular workplace.

Glare calculation software can work in several modes. In a grid mode, a grid of viewing points is selected and the GI values are calculated in the C0 or C90 planes. In a radial mode, GI values are calculated at a specified location at 45 degree intervals around the full field of view, identifying the maximum. In a find mode the designer sets a threshold, below which results are not shown, and the program reports the location and viewing direction of the maximum GI value.

How Glare Index aids productivity

The consequences of discomfort glare appear to be an increase in headaches and other physical symptoms, a lowering of tolerance and an increase in tension between people at work. The situation can be aggravated by other stresses such as noise, uncomfortable thermal conditions and poor ergonomic layout.

People cannot work productively if their visual environment is of poor quality. As far as the illuminated working environment is concerned, the Glare Index system is a sensitive and easy-to-use indicator of the locations and viewing directions likely to produce high glare values, which are not conducive to productivity or good visual performance.