Why the standard exists
The fires occurred mainly in Europe. The most infamous in Australia was at the Whiskey Au Go Go night club in Brisbane on 8 March 1973. In almost every case it was established that the main cause of death was either people being trampled while trying to escape, or the effects of smoke inhalation as they tried in vain to find the exits.
The LG/7 committee
In 1976 Standards Australia formed a committee known as LG/7 to examine the possibility of an Australian code of practice for evacuation lighting. Its role was to develop means by which people could escape from any building under threat from fire. It was not intended to directly assist firefighters or rescue workers, nor to allow work to continue. The foreword of AS 2293 spells out the difference between standby, safety and evacuation lighting.
Working Group 1 first considered the fundamental questions of how much light would be needed to safely evacuate people from a building, and how a system would be assessed for compliance, both at the design stage and when the project was completed.
Putting numbers to the problem
In the late 1970s there were three major international proposals. The British had a recommended minimum of 0.2 lux. The American proposal had an average of one foot candle, approximately 10 lux. The Russians required one tenth of the normal average illuminance. The three meant a wide variation not only in illuminance but in the cost of installations and battery capacities.
The 0.2 lux proposition was the most attractive, but it was realised that it would be very difficult to measure or design accurately. The committee was also concerned that a sudden change from 400 lux in a typical office to 0.2 lux might induce panic. To test these questions, trials were carried out in Melbourne with members of the Illuminating Engineering Society as participants and observers. The results can be summarised as follows:
- People of all ages could adapt from 400 lux to 0.2 lux in a few seconds without undue difficulty.
- It is important that vertical surfaces such as walls and doors be recognisable, to assist in orientation.
- Emergency lighting must be integrated with exit signs, with a direct line of sight to the exit sign or to directional signs pointing to it.
- Using conventional instruments, it is almost impossible to accurately measure illuminance in the order of one lux or less.
- Emergency lighting should be activated within 1 second of the failure of the mains lighting, and reach at least 50% capacity within 5 seconds.
The committee was impressed with experimental work in the United Kingdom which concluded that 0.28 lux was a safe minimum illuminance, and that a variation in illuminance along an escape route approaching 50:1 had no effect on the ability to see.
It was found that the onset of panic in a crowd was caused by a number of factors, including loss of orientation, a feeling of isolation and an awareness that seconds seemed interminable. These effects are heightened by the presence, or even the smell, of smoke. On smoke itself, the committee concluded there was no practical way of ensuring the lighting system would remain effective, and that dependence must be placed on building construction and ventilation to keep escape paths as free of smoke as possible.
The people checking a design would mainly be building surveyors and inspectors with little lighting knowledge. This led to the tables of maximum spacing for a given mounting height and luminaire classification. From the 1995 edition of AS/NZS 2293, illuminance calculations by a computer-aided design program or point-by-point calculation are also permissible.
Classifying emergency luminaires
Appendix C of AS/NZS 2293.3 explains the classification of emergency luminaires using an alphanumeric system. The letter, A to E, defines the general shape of the intensity distribution curve, considered in both the C0 and C90 planes. For each class a formula gives the minimum luminous intensity (Ip) at a given angle γ from the downward vertical, relative to the assigned intensity in the downward vertical direction (I0).
| Class | Formula | Range |
|---|---|---|
| A | Ip = I0 × cos⁴(γ) | γ ≤ 70° |
| B | Ip = I0 × cos³(γ) | γ ≤ 70° |
| C | Ip = I0 × cos(γ) to the power 1.5 | γ ≤ 70° |
| D | Ip = I0 × (2 + cos(γ)) ÷ 3 | γ ≤ 70° |
| E | Ip = I0 × (1 + 0.04γ ÷ 30) | γ ≤ 30° |
| E | Ip = 1.07 × I0 × cos(2.6 × (γ − 35)) | 30° ≤ γ ≤ 65° |
The numerical part of the classification is based on the R10 series of preferred numbers (1.0, 1.25, 1.6, 2.0, 2.5, 3.2, 4.0, 5.0, 6.3, 8.0). It is an assigned number, which must be equal to or less than the actual luminous intensity in the downward vertical direction. A classification of D63 means the distribution of the luminaire satisfies the Classification D equation with I0 = 63 cd.
An example classification
Consider a luminaire with the measured intensity values below.
| Gamma angle (deg) | C0 intensity (cd) | C90 intensity (cd) |
|---|---|---|
| 0 | 128 | 128 |
| 10 | 126 | 125 |
| 20 | 115 | 118 |
| 30 | 86 | 107 |
| 40 | 54 | 90 |
| 50 | 27 | 49 |
| 60 | 9 | 15 |
| 70 | 4 | 6 |
| 80 | 2 | 4 |
| 90 | 0 | 0 |
Assuming a mounting height of 2.7 m, the spacings for the classifications that can be assigned are as follows.
| C0 classification | C0 spacing (m) | C90 classification | C90 spacing (m) |
|---|---|---|---|
| A125 | 9.9 | A125 | 9.9 |
| B63 | 10.0 | B100 | 11.0 |
| C16 | 9.3 | D6.3 | 9.0 |
| D5 | 8.1 | D6.3 | 9.0 |
| E20 | 10.4 | E32 | 11.2 |
Even with a downward intensity of 128 cd, the shape of the C0 curve is such that it can only be assigned a D5 classification, giving a maximum spacing of 8.1 m. The best maximum spacing in the C0 direction comes from the E classification, E20, at 10.4 m. In the C90 direction the best is 11.2 m, from an E32 classification. The luminaire is therefore assigned a classification of C0 = E20, C90 = E32.